System Setup
You must perform the following before operating the system:
• If generator is installed in an area regularly subjected
to temperatures below 4°C, select a 50 second warm
up time by moving jumper installed on JP2 from ‘20’
position to ‘50’ position.
• Set the DPSW1 and DPSW2 dipswitches on the control
module to match the KW rating of the Home Standby
Generator set as described in Setting Dipswitches.
Setting Dipswitches
Dipswitches are used to adjust control board operation
based on generator capacity and fuel source. Sum of DSPW1
and DPSW2 are set to correspond to system kW rating.
Dipswitch DPSW1 has units of 1,000 Watts; Dipswitch
DPSW2 has units of 10,000 Watts.
IMPORTANT: Set only one switch to Onposition on each
dipswitch.
NOTICE
Use extreme caution when setting dipswitches or
damage to control board will result.
Use a pencil or small piece of plastic to set the dipswitch.
NEVER use a screwdriver or any type of metal object to
set dipswitches.
TheOn position for the dipswitches is the switch number
ON THE CONTROL BOARD, not on the switch. For example,
on a 27,000 Watt generator that runs on natural gas (NG), set
DPSW2 dipswitch 20 to “On” position. Set DPSW1 dipswitch
7 to “On” position. 20,000 plus 7000 equals 27,000 Watts.
Supervisory Control Wiring
1. Terminal strip on control module in transfer switch
has four connections for customer use. There are two
sets of “Normally Closed” contacts available. They will
be activated when generator power is required. These
can be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.
NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.
2. Terminals “A-A” on control module are rated for
24 VAC and air conditioner contactor control. Contacts
are connected in series with the air conditioner
contactor control circuit.
3. Terminals “B-B” on control module are rated for 5 Amp
250 VAC and installer supplied contactor to control a
large load. Example: electric hot water heater. Contacts
are connected in series with the contactor control circuit.
4. Tighten all wire connections/fasteners to proper torque.
See inside transfer switch enclosure for proper torque
values.
JP2
DPSW2
Dipswitch
DPSW1
Dipswitch
CT1 & CT2
Connectors
Supervisory
Contacts
A
A
Air Conditioner Contactor
24 VAC
B
B
Contactor
230 VAC
230 VAC