Main Distribution Panel
To Generator
Neutral
Terminal
Supervisory
Contacts
To Utility Power
Generator
Connection
Utility
Connection
Ground
Terminal
230V Generator
Connection
Main
Ground Bus
Wireway
Load
Connection
CT 2
CT 1
Generator Tx Rx and
Tx Rx Ground Connection
Ground
N2
N1
T1
T2
Ground
GND
E1
E2
F1
F2
Tx Rx
Tx Rx GND
Connector tightening torques shall be as follows:
Utility 5.5 Nm Ground 5.5 Nm
Generator 5.5 Nm Control 1.4 Nm
Neutral 12.5 Nm Fuseblocks 1.4 Nm
Use oxide inhibitor on all aluminum terminations.
All terminal and bus lugs are suitable for copper wire of
60°/75°C rating.